feature #36
openfeature #16: ENERGY METER SELECTION
Energy Meter SELEC EM2M & EM368 Integration with DCN (ESP32)
0%
Description
1️⃣ Energy Meter Integration with DCN (ESP32)
Overview
The DCN integrates with the EM2M & EM368 Select Energy Meter to collect electrical parameters using RS485 Modbus RTU communication. The ESP32 periodically polls the energy meter and stores readings for reporting and analytics and setting page to configure
Communication Architecture
Controller: ESP32
Protocol: Modbus RTU
Physical Layer: RS485
Baud Rate: Configurable (Default 9600)
Slave Address: Configurable
Data Acquisition
ESP32 polls the energy meter registers to acquire:
Parameter Description
Voltage (L1, L2, L3) Phase voltage readings
Current (L1, L2, L3) Load current through CT
Active Power (kW) Real power consumption
Reactive Power (kVAR) Reactive power
Apparent Power (kVA) Apparent load
Power Factor System efficiency
Frequency Supply frequency
Energy (kWh) Total energy consumed
ESP32 Firmware Tasks
Initialize RS485 UART communication
Poll registers at configurable intervals
Validate CRC of Modbus frames
Convert raw register data to engineering values
Store readings in DCN data buffer
Forward data for report generation and graph logging
Updated by hemant harlalka 3 months ago
- Due date set to 03/09/2026
- Start date changed from 03/12/2026 to 03/04/2026
- Parent task set to #16